Mosebach is proud to present its Radiator Mounted Resistive RadBANK™.

RadBANK™
is a resistive, continuous duty, forced-air-cooled load bank that can be used to periodically test the generator or to add additional load to minimize diesel engine “wet stacking” problems, which is the primary cause of premature diesel engine failures. RadBANK™ is intended to be mounted directly to the engine radiator of the generator set. It will use the engine’s radiator air flow to cool the resistive load elements, and it is intended for use indoors or outdoors.

Each RadBANK™ is controlled from a control box, conveniently located on the side of the unit and placed in a NEMA 3R enclosure with easy access to RadBANK™ master ON/OFF switch, airflow lamp and individual Load Step ON/OFF switches.

All of our load banks are designed to apply a selectable resistive load with various power step resolutions to a power source, manually or remotely.

The long operating life of resistors in all of our load banks is achieved through various Mosebach innovations and extensive experience of over 80 years in resistor design and construction.


Voltage:
As required: 240, 480, 600V or other.

Controls:
Are conveniently placed in a NEMA 3R enclosure with easy access to RadBANK™ master ON/OFF switch, airflow lamp and individual Load Step ON/OFF switches. Based on your preference the control box can be mounted in Mounting Position #1 or #2.

Control Power:
Dependent on customer requirements, typically 120V.

Resistive Load Elements:
All of our High-Power elements are made with Mosebach’s WeldlessWeave™, a technology that we have refined over 80 years of building and designing resistors for use in the toughest environments, such as locomotives and giant mining trucks. Our WeldlessWeave™ technology utilizes a continuous ribbon to eliminate all welds. By eliminating welds, hot spots are eliminated. In addition to our WeldlessWeave™ technology, Mosebach uses its Slimline™ innovation to provide power resistance in even smaller spaces. All of our elements are easily and individually replaceable. We are so confident in our WeldlessWeave™ that we offer a 5-year warranty on all resistive load elements.

Cooling: RadBANK™
will be directly mounted to the engine radiator of the generator set. It will use the engine’s radiator air flow to cool the resistive load elements.

RadBANK™ Models:
Available in standard sizes ranging from 10kW to 1000kW and up. Please contact us with your high capacity application requirements!

Load Steps:
Our standard load steps are 90kW, 45kW, 25kW, 10kW and 5kW.

Frame Construction, Size and Installation:
The load bank structure is constructed with a sturdy steelangle frame. Each frame is fabricated to fit the particular application.

Handling:
Handling is provided by 2 heavy-duty lifting eyes.

Safety:
Air pressure switch to detect positive airflow, and fuses on the main line. Branch circuit fusing is optional.

Options:
Louvers for added protection against weather, remote controls and metering, auto/manual control option, auto-dump, and branch circuit fusing.

Warranty:
One year for material and workmanship. Five years for resistor elements.